Manual No.
I66E-EN-01
VARISPEEDꢀF7
The Industrial Workhorse
Model: CIMR-F7Z
200V Class 3-phase 0.4 to 110 kW
400V Class 3-phase 0.4 to 300 kW
QuIckꢀSTARTꢀGuIDEꢀ
F7Z Quick Start Guide
Table of Contents
‹ Safety Precautions and Instructions ........................................................................... EN-3
‹ EMC Compatibility ...................................................................................................... EN-4
‹ Mechanical Installation ............................................................................................... EN-6
‹ Electrical Connection .................................................................................................. EN-8
‹ Wiring Main Circuit Inputs ........................................................................................ EN-12
‹ Digital Operator Display (optional) ............................................................................ EN-14
‹ Start Up Procedure .................................................................................................. EN-15
‹ Before Power Up ...................................................................................................... EN-16
‹ Display after Power Up ............................................................................................. EN-16
‹ Autotuning ................................................................................................................ EN-16
‹ General Faults and Alarms ....................................................................................... EN-22
‹ Operator Programming Errors .................................................................................. EN-24
Warnings
CAUTION
Cables must not be connected or disconnected, nor signal tests carried out,
while the power is switched on.
The Varispeed F7 DC bus capacitor remains charged even after the power has been
switched off. To avoid an electric shock hazard, disconnect the frequency inverter from the
mains before carrying out maintenance. Then wait for at least 5 minutes after all LEDs
have gone out.
Do not perform a withstand voltage test on any part of the Varispeed. The frequency
inverter contains semiconductors, which are not designed for such high voltages.
Do not remove the digital operator while the mains supply is switched on. The printed cir-
cuit board must also not be touched while the inverter is connected to the power.
Never connect general LC/RC interference suppression filters, capacitors or overvoltage
protection devices to the inverter input or output.
To avoid unnecessary overcurrent faults, etc. being displayed, the signaling contacts of any
contactor or switch fitted between inverter and motor must be integrated into the inverter
control logic (e.g. baseblock).
This is absolutely imperative!
This manual must be read thoroughly before connecting and operating the inverter. All
safety precautions and instructions for use must be followed.
The inverter may must be operated with the appropriate line filters, following the installation
instructions in this manual and with all covers closed and terminals covered.
Only then will adequate protection be provided. Please do not connect or operate any
equipment with visible damage or missing parts. The operating company is responsible
for any injuries or equipment damage resulting from failure to heed the warnings in this
manual.
EN-2
‹ Safety Precautions and Instructions
„ General
Please read these safety precautions and instructions for use thoroughly before installing and oper-
ating this inverter. Also read all of the warning signs on the inverter and ensure they are never dam-
aged or removed.
Live and hot inverter components may be accessible during operation. Removal of housing compo-
nents, the digital operator or terminal covers runs the risk of serious injuries or damage in the event
of incorrect installation or operation. The fact that frequency inverters control rotating mechanical
machine components can give rise to other dangers.
The instructions in this manual must be followed. Installation, operation and maintenance may only
be carried out by qualified personnel. For the purposes of the safety precautions, qualified personnel
are defined as individuals who are familiar with the installation, starting, operation and maintenance
of frequency inverters and have the proper qualifications for this work. Safe operation of these units
is only possible if they are used properly for their intended purpose.
The DC bus capacitors can remain live for about 5 minutes after the inverter is disconnected from
the power. It is therefore necessary to wait for this time before opening its covers. All of the main cir-
cuit terminals may still carry dangerous voltages.
Children and other unauthorized persons must not be allowed access to these inverters.
Keep these Safety Precautions and Instructions for Use readily accessible and supply them to all
persons with any form of access to the inverters.
„ Intended Use
Frequency inverters are intended for installation in electrical systems or machinery.
Their installation in machinery and systems must conform to the following product standards of the
Low Voltage Directive:
EN 50178, 1997-10, Equipping of Power Systems with Electronic Devices
EN 60204-1, 1997-12Machine Safety and Equipping with Electrical Devices
Part 1: General Requirements (IEC 60204-1:1997)/
Please note: Includes Corrigendum of September 1998
EN 61010-1, A2, 1995Safety Requirements for Information Technology Equipment
(IEC 950, 1991 + A1, 1992 + A2, 1993 + A3, 1995 + A4, 1996, modified)
CE marking is carried out to EN 50178, using the line filters specified in this manual and following
the appropriate installation instructions.
„ Transportation and storage
The instructions for transportation, storage and proper handling must be followed in accordance with
the technical data.
„ Installation
Install and cool the inverters as specified in the documentation. The cooling air must flow in the
specified direction. The inverter may therefore only be operated in the specified position (e.g.
upright). Maintain the specified clearances. Protect the inverters against impermissible loads. Com-
ponents must not be bent nor insulation clearances changed. To avoid damage being caused by
static electricity, do not touch any electronic components or contacts.
EN-3
„ Electrical Connection
Carry out any work on live equipment in compliance with the national safety and accident prevention
regulations. Carry out electrical installation in compliance with the relevant regulations. In particular,
follow the installation instructions ensuring electromagnetic compatibility (EMC), e.g. shielding,
grounding, filter arrangement and laying of cables. This also applies to equipment with the CE mark.
It is the responsibility of the manufacturer of the system or machine to ensure conformity with EMC
limits.
Your supplier or Omron Yaskawa Motion Control representative must be contacted when using leak-
age current circuit breaker in conjunction with frequency inverters.
In certain systems it may be necessary to use additional monitoring and safety devices in compli-
ance with the relevant safety and accident prevention regulations. The frequency inverter hardware
must not be modified.
„ Notes
The Varispeed F7 frequency inverters are certified to CE, UL, and cUL
‹ EMC Compatibility
„ Introduction
This manual was compiled to help system manufacturers using OMRON YASKAWA Motion Control
(OYMC) frequency inverters design and install electrical switch gear. It also describes the measures
necessary to comply with the EMC Directive. The manual's installation and wiring instructions must
therefore be followed.
Our products are tested by authorized bodies using the standards listed below.
Product standard: EN 61800-3:1996
EN 61800-3; A11:2000
„ Measures to Ensure Conformity of OYMC Frequency inverters to the EMC Directive
OYMC frequency inverters do not necessarily have to be installed in a switch cabinet.
It is not possible to give detailed instructions for all of the possible types of installation. This manual
therefore has to be limited to general guidelines.
All electrical equipment produces radio and line-borne interference at various frequencies. The
cables pass this on to the environment like an aerial.
Connecting an item of electrical equipment (e.g. drive) to a supply without a line filter can therefore
allow HF or LF interference to get into the mains.
The basic countermeasures are isolation of the wiring of control and power components, proper
grounding and shielding of cables.
A large contact area is necessary for low-impedance grounding of HF interference. The use of
grounding straps instead of cables is therefore definitely advisable.
Moreover, cable shields must be connected with purpose-made ground clips.
EN-4
„ Laying Cables
Measures Against Line-Borne Interference:
Line filter and frequency inverter must be mounted on the same metal plate. Mount the two compo-
nents as close to each other as possible, with cables kept as short as possible.
Use a power cable with well-grounded shield. For motor cables up to 50 meters in length use
shielded cables. Arrange all grounds so as to maximize the area of the end of the lead in contact
with the ground terminal (e.g. metal plate).
Shielded Cable:
• Use a cable with braided shield.
• Ground the maximum possible area of the shield. It is advisable to ground the shield by connect-
ing the cable to the ground plate with metal clips (see following figure).
Ground Plate
Ground Clip
Fig 1 Earthing the cable shield with metal clips
The grounding surfaces must be highly conductive bare metal. Remove any coats of varnish and
paint.
– Ground the cable shields at both ends.
– Ground the motor of the machine.
EN-5
Installation
‹ Mechanical Installation
„ Unpacking the Inverter
Check the following items after unpacking the inverter.
Item
Method
Has the correct Inverter model been
delivered?
Check the model number on the nameplate on the side of the
Inverter.
Inspect the entire exterior of the Inverter to see if there are any
scratches or other damage resulting from shipping.
Is the Inverter damaged in any way?
Are any screws or other components
loose?
Use a screwdriver or other tools to check for tightness.
If any irregularities in the above items are found, contact the agency from which the Inverter was pur-
chased or your Omron Yaskawa Motion Control representative immediately.
„ Checking the Installation Site
Protection covers are attached to the top and bottom of the NEMA 1 / IP20 Inverters. Be sure to
remove the top cover before operating a 200 or 400 V Class Inverter with a capacity of 18.5 kW or
less inside a panel.
Observe the following precautions when mounting the Inverter:
• Install the Inverter in a clean location which is free from oil mist and dust. It can be installed in a
totally enclosed panel that is completely shielded from floating dust.
• When installing or operating the Inverter, always take special care so that metal powder, oil,
water, or other foreign matter does enter the Inverter.
• Do not install the Inverter on combustible material, such as wood.
• Install the Inverter in a location free from radioactive materials and combustible materials.
• Install the Inverter in a location free from harmful gasses and liquids.
• Install the Inverter in a location without excessive oscillation.
• Install the Inverter in a location free from chlorides.
• Install the Inverter in a location without direct sunlight.
EN-6
„ Installation Orientation
Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter,
always provide the following installation space to allow normal heat dissipation.
A
B
Air
A
B
200V class inverter, 0.55 to 90 kW
400V class inverter, 0.55 to 132 kW
200V class inverter, 110 kW
400V class inverter, 160 to 220 kW
400V class inverter, 300 kW
50 mm 120 mm
120 mm 120 mm
300 mm 300 mm
30mm min.
120mm min.
30mm min.
50mm
min.
Air
Horizontal Space
Vertical Space
Fig 2 Installation space
1. The same space is required horizontally and vertically for IP00, IP20 and NEMA 1 Inverters.
2. Always remove the top protection cover after installing an Inverter with an output of 18.5 kW or less in a
panel.
Always provide enough space for suspension eye bolts and the main circuit lines when installing an
Inverter with an output of 22 kW or more in a panel.
IMPORTANT
„ Installation of Inverters and EMC filters
PE L2
L1
For an EMC rules compliant installation
consider the following points:
L3
Ground Bonds
Remove any paint!
• Use a line filter.
• Use shielded motor cables.
PE
• Mount the inverter and filter on a
grounded cunductive plate.
Line
• Remove any paint or dirt before mount-
ing the parts in order to reach the low-
est possible grounding impedance.
Inverter
Filter
L2
L1 L3
V
Load
GND
U
W
GND
Cable Lenght
as short as possible
Grounded
Metal Plate
Screened
Motor cable
Ground Bonds
Remove any paint!
M
~3
Fig 3 EMC filter installation
EN-7
‹ Electrical Connection
„Wiring the Inverter
DC reactor to improve input
power factor (optional)
Braking resistor unit (optional)
Short-circuit bar
Main Contactor
B1
B2
2
T
1
Fuses
R/L1
U/T1
V/T2
W/T3
L1
L2
L3
3-phase power
380 to 480 V
50/60 Hz
Line
Filter
S/L2
M
T/L3
Varispeed F7
PE
Forward Run / Stop
S1
S2
S3
S4
S5
S6
S7
SN
SC
SP
MA
MB
MC
Fault relay output
250 VAC, 1 A max.
30 VDC, 1 A max.
Reverse Run / Stop
External Fault
Fault reset
Multi-function
M1
M2
Multi-step speed setting 1
digital inputs
Relay output 1
[Factory setting]
[Default: Running]
Multi-step speed setting 2
M3
Jog frequency selection
Relay output 2
[Default: Zero speed]
Multi-function digital output
250 VAC, 1 A max.
M4
30 VDC, 1 A max.
M5
M6
Relay output 3
[Default:
Frequency agree 1]
24 V
E(G)
Shield
terminal
2CN
Pulse train input [Default:
Frequency reference input]
0 to 32 kHz
RP
+V
Analog input setting
adjustment
PG
Option
Card
Analog input power supply
15 V, 20 mA
2 kΩ
Analog input 1: Master
frequency reference
0 to 10 V (20 kΩ)
0 to 10 V
A1
2 k
Ω
Multi-function analog input 2
[Default: Frequency bias
4 to 20 mA (20 kΩ)]
4 to 20 mA
A2
P
P
AC
0 V
-V
Analog input power supply
-15 V, 20 mA
E(G)
Shield
terminal
Input
Option
Card
MP
AC
Pulse train output
0 to 32 kHz (2.20 kΩ)
[Default: Output frequency]
Adjustment,
20 k
Ω
-
-
Multi-function analog output 1
(-10 to +10 V, 2 mA / 4 to 20 mA)
[Default: Output frequency, 0 to 10 V)
4 to 20 mA (20 kΩ)]
+
FM
FM
Terminating
resistance
Adjustment,
20 k
R+
R-
Ω
P
P
+
Multi-function analog output 2
(-10 to +10 V, 2 mA / 4 to 20 mA)
[Default: Output current, 0 to 10 V)
4 to 20 mA (20 kΩ)]
AM
AC
MEMOBUS
communication
RS-485/422
AM
S+
S-
IG
Twisted-pair
shielded wires
Shielded
wires
P
Fig 4 Wiring Diagram
EN-8
„Main Circuit Terminals
Main circuit terminal functions are summarized according to terminal symbols in Table 1. Wire the
terminals correctly for the desired purposes.
Table 1 Main Circuit Terminal Functions (200 V Class and 400 V Class)
Model: CIMR-F7Z††††
Purpose
Terminal Symbol
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
200 V Class
20P4 to 2110
2022 to 2110
20P4 to 2110
400 V Class
40P4 to 4300
4022 to 4300
40P4 to 4300
Main circuit power input
Inverter outputs
DC bus terminals
20P4 to 2110
40P4 to 4300
1,
Braking Resistor Unit Connec-
tion
B1, B2
20P4 to 2018
40P4 to 4018
DC reactor connection
Braking Unit connection
Ground
20P4 to 2018
2022 to 2110
20P4 to 2110
40P4 to 4018
4022 to 4300
40P4 to 4300
1,
3,
2
„Control Circuit Terminals
Fig 5 shows the control terminal arrangement. The functions of the control circuit terminals are
shown in Table 2. Use the appropriate terminals for the correct purposes.
Fig 5 Control terminal arrangement
Table 2 Control Circuit Terminals with default settings
Type
No.
Signal Name
Function
Forward run when ON; stopped when
OFF.
Signal Level
S1 Forward run/stop command
Reverse run when ON; stopped when
OFF.
S2 Reverse run/stop command
*1
S3
S4
Fault when ON.
Reset when ON
External fault input
Fault reset *1
24 VDC, 8 mA
Photocoupler isolation
Multi-step speed reference 1
*1
Functions are
selected by set-
ting H1-01 to
H1-05.
Auxiliary frequency ref-
erence when ON.
S5
(Master/auxiliary switch)
Multi-step speed 2
when ON.
Multi-step speed reference 2
*1
S6
S7
Jog frequency when
ON.
Jog frequency reference *1
SC Digital input common
SN Digital Input Neutral
–
–
–
–
24 VDC, 250 mA max.
SP Digital Input Power Supply
+V 15 V power output
+24VDC power supply for digital inputs
*2
15 V power supply for analog references 15 V (Max. curr.: 20mA)
-10 to +10 V (20 kΩ)
0 to +10 V (20 kΩ)
A1 Frequency reference
0 to +10 V/100%
Auxiliary analog fre-
quency reference;
4 to 20 mA (250Ω)
Function is
selected by set- 0 V to +10 V (20 kΩ)
ting H3-09.
4 to 20 mA (250 Ω)
Auxiliary Frequency Refer-
ence
A2
0 to 20 mA (250 Ω)
-V
-15 V power output
-15 V power supply for analog references
–
AC Analog reference common
–
–
Shield wire, optional ground
E(G)
–
line connection point
EN-9
Type
No.
M1
Signal Name
Function
Signal Level
During run (NO)
Closed during Run
M2
M3
Closed when output
Function
Zero speed (NO)
frequency at zero level selected by H2-
Relay contacts
Contact capacity:
1 A max. at 250 VAC
M4
(b2-01) or below
01 to H2-03
M5
M6
MA
Speed agreement detection Within 2 Hz of set fre-
(NO) quency when ON
*3
1 A max. at 30 VDC
Closed across MA and MC during faults
Open across MB and MC during faults
MB Fault output signal
MC
Analog output fre-
quency signal;
0 to 10 V; 10V=FMAX H4-01
Function
selected by
0 to +10 V max. 5%
2 mA max.
FM Output frequency
AC Analog common
–
-10 to +10 V max. 5%
2 mA max
Analog output power
signal;
0 to 10V; 10V=max.
appl. motor capacity
Function
selected by
H4-04
AM Inverter output power
4 to 20 mA
0 to 32 kHz (3kΩ)
High level voltage 3.5 to
13.2 V
*4
RP Pulse Input
H6-01 (Frequency reference input)
H6-06 (Output frequency)
0 to 32 kHz
+15 V output (2.2kΩ)
MP Pulse Output
R+
R-
S+
S-
MEMOBUS communications
input
Differential input,
PHC isolation
For 2-wire RS-485, short R+ and S+
as well as R- and S-.
MEMOBUS communications
output
Differential input,
PHC isolation
IG
Signal common
–
–
*1. The default settings are given for terminals S3 to S7. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-
step speed setting
1 for S6 and multi-step speed setting 2 for S7.
*2. Do not use this power supply for supplying any external equipment.
*3. When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode as shown in Fig 6
*4. Pulse input specifications are given in the following table:
Low level voltage
High level voltage
H duty
0.0 to 0.8 V
3.5 to 13.2 V
30% to 70%
0 to 32 kHz
Pulse frequency
Flywheel diode
The rating of the flywheel diode must
be at least as high as the circuit volt-
age.
Coil
External power:
30 VDC max.
1 A max.
Fig 6 Flywheel Diode Connection
1. In Fig 4 the wiring of the digital inputs S1 to S7 is shown for the connection of contacts or NPN transis-
tors (0V common and sinking mode). This is the default setting.
2. A DC reactor is an option only for Inverters of 18.5 kW or less. Remove the short circuit bar when con-
necting a DC reactor.
IMPORTANT
EN-10
„ Sinking/Sourcing Mode (NPN/PNP Selection)
The input terminal logic can be switched over between sinking mode (0-V common, NPN) and
sourcing mode (+24V common, PNP) by using the jumper CN5. An external power supply is also
supported, providing more freedom in signal input methods.
Table 3 Sinking / Sourcing Mode and Input Signals
Internal Power Source - Sinking Mode (NPN)
External Power Source - Sinking Mode (NPN)
External +24 V
Internal Power Source - Sourcing Mode (PNP)
External Power Source - Sourcing Mode (PNP)
External +24 V
EN-11
‹ Wiring Main Circuit Inputs
Installing Fuses
To protect the inverter, it is recommended to use semiconductor fuses like they are shown in the
table below.
Table 4 Input Fuse Selection
RatedInverter
Fuse Selection
Current (A)
Selection Example (Ferraz)
Inverter Type
Output
Current (A)
3.2
I2t (A2s)
I2t (A2s)
Voltage (V)
Model
Rating
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
2045
2055
2075
2090
2110
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
10
10
15
20
30
40
60
80
100
130
150
180
240
300
350
450
550
600
12~25
12~25
23~55
34~98
82~220
A60Q12-2
A60Q12-2
A60Q15-2
A60Q20-2
A60Q30-2
A50P50-4
A50P80-4
A50P80-4
A50P125-4
A50P150-4
A50P150-4
A50P200-4
A50P250-4
A50P300-4
A50P350-4
A50P450-4
600V / 12A
600V / 12A
600V / 15A
600V / 20A
600V / 30A
500V / 50A
500V / 80A
500V / 80A
500V / 125A
500V / 150A
500V / 150A
500V / 200A
500V/ 250A
500V / 300A
500V / 350A
500V / 450A
500V / 600A
500V / 600A
17
17
26
41
132
250
640
640
4.1
7.0
9.6
15
23
31
45
58
220~610
290~1300
450~5000
1200~7200
1800~7200
870~16200
1500~23000
2100~19000
2700~55000
4000~55000
7100~64000
1600
2200
2200
4000
6200
9000
12000
20000
36000
36000
71
85
115
145
180
215
283
346
415
11000~64000 A50P600-4
13000~83000 A50P600-4
40P4
40P7
41P5
42P2
43P7
44P0
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
4055
4075
4090
4110
4132
1.8
2.1
3.7
5.3
7.6
8.7
12.5
17
24
31
39
45
60
75
91
112
150
180
216
260
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
5
5
10
10
15
20
25
30
50
60
70
80
100
125
150
150
250
300
350
400
6~55
6~55
10~55
18~55
34~72
A60Q10-2
A60Q10-2
A60Q12-2
A60Q15-2
A60Q20-2
A60Q30-2
A60Q30-2
A60Q30-2
A70P50-4
A70P70-4
A70P80-4
A70P80-4
A70P100-4
A70P125-4
A70P150-4
A70P200-4
A70P250-4
A70P300-4
A70P350-4
A70P400-4
600V / 10A
600V / 10A
600V / 12A
600V / 15A
600V / 20A
600V / 30A
600V / 30A
600V / 30A
700V / 50A
700V / 70A
700V / 80A
700V / 80A
700V / 100A
700V / 125A
700V / 150A
700V / 200A
700V / 250A
700V / 300A
700V / 350A
700V / 400A
10
10
17
26
41
132
132
132
300
50~570
100~570
100~640
150~1300
400~1800
700~4100
240~5800
500~5800
750~5800
920~13000
1500~13000
3000~55000
3800~55000
5400~23000
7900~64000
590
770
770
1200
1900
2700
4800
7500
11000
15000
19000
14000~25000
0
20000~25000
0
34000~40000
0
52000~92000
0
4160
4185
4220
4300
304
370
506
675
480
480
480
480
450
600
700
900
A70P450-4
A70P600-4
A70P700-4
A70P900-4
700V / 450A
700V / 600A
700V / 700A
700V / 900A
24000
43000
59000
97000
Consider the following precautions for the main circuit power supply input.
• If a moulded case circuit breaker is used for the power supply connection (R/L1, S/L2, and T/L3),
ensure that the circuit breaker is suitable for the Inverter.
EN-12
• If an earth leakage breaker is used, it should be able to detect all kinds of current in order to
ensure a safe earth leakage current detection
• A magnetic contactor or other switching device can be used at the inverter input. The inverter
should not be powered up more than once per hour.
• The input phases (R/S/T) can be connected in any sequence.
• If the Inverter is connected to a large-capacity power transformer (600 kW or more) or a phase
advancing capacitor is switched nearby, an excessive peak current could flow through the input
power circuit, causing an inverter damage. As a countermeasure install an optional AC Reactor
at the inverter input or a DC reactor at the DC reactor connection terminals.
• Use a surge absorber or diode for inductive loads near the Inverter. Inductive loads include mag-
netic contactors, electromagnetic relays, solenoid valves, solenoids, and magnetic brakes.
„Wiring the Output Side of the Main Circuit
The following precautions should be considered for the output circuit wiring.
• Never connect any power source to the inverter output terminals. Otherwise the inverter can be
damaged.
• Never short or ground the output terminals. Otherwise the inverter can be damaged.
• Do not use phase correction capacitors. Otherwise the inverter and capacitors can be damaged.
• Check the control sequence to make sure, that the magnetic contactor (MC) between the Inverter
and motor is not turned ON or OFF during inverter operation. If the MC is turned ON during the
Inverter is operation, a large inrush current will be created and the inverter’s overcurrent protec-
tion may operate.
„Ground Connection
The following precautions should be considered for the ground connection.
• Do not share the ground wire with other devices, such as welding machines or power tools.
• Always use a ground wire, that complies with technical standards on electrical equipment and
minimize the length of the ground wire.
Leakage current is caused by the Inverter. Therefore, if the distance between the ground elec-
trode and the ground terminal is too long, potential on the ground terminal of the Inverter will
become unstable.
• When more than one Inverter is used, do not to loop the ground wire.
OK
NO
Fig 7 Ground Wiring
„Control Circuit Wiring Precautions
Consider the following precautions for wiring the control circuits.
• Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1,
V/T2, W/T3, B1, B2,
,
1, 2, and 3, PO, NO) and other high-power lines.
• Separate wiring for control circuit terminals MA, MB, MC, M1 to M6 (relay outputs) from wiring to
other control circuit terminals.
• If an optional external power supply is used, it should be a UL Listed Class 2 power supply.
• Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.
• Ground the cable shields with the maximum contact area of the shield and ground.
• Cable shields have to be grounded on both cable ends.
EN-13
Keypad Operation
‹ Digital Operator Display (optional)
The key names and functions of the Digital Operator are described below
Drive Mode Indicators
FWD: Lights up when a forward run command is
input.
REV:
SEQ:
REF:
Lights up when a reverse run command is
input.
Lights up when any other run command
source than the Digital Operator is selected.
Lights up when any other frequency reference
source than the Digital Operator is selected.
ALARM: Lights up when an error or alarm has
occurred.
Data Display
Displays monitor data, parameter numbers, and set-
tings.
Mode Display (displayed at the upper left of the data display
DRIVE: Lights up in Drive Mode.
QUICK: Lights up in Quick Programming Mode.
ADV:
Lights up in Advanced Programming Mode.
VERIFY:Lights up in Verify Mode.
A. TUNE:Lights up in Autotuning Mode.
Keys
Execute operations such as setting user parameters,
monitoring, jogging, and autotuning.
„Digital Operator Keys
Key
Name
Function
Switches between operation via the Digital Operator (LOCAL) and
LOCAL/REMOTE Key the settings in b1-01 and b1-02 (REMOTE).
This key can be enabled or disabled by setting parameter o2-01.
MENU Key
Selects the modes.
ESC Key
Returns to the status before the DATA/ENTER Key was pressed.
Enables jog operation when the Inverter is being operated from the
Digital Operator.
JOG Key
Selects the rotation direction of the motor when the Inverter is being
operated from the Digital Operator.
FWD/REV Key
Shift/RESET Key
Sets the active digit when programming user parameters.
Also acts as the Reset key when a fault has occurred.
Selects user parameter numbers and increments parameter set-
Increment Key
Decrement Key
tings.
Used to move to the next item or data.
Selects user parameter numbers and decrements parameter set-
tings.
Used to move to the previous item or data.
DATA/ENTER Key
RUN Key
Enters menus and parameters and validates parameter settings.
Starts operation when the Inverter is being controlled by the Digital
Operator (LOCAL Mode).
Stops Inverter operation (LOCAL and REMOTE Mode).
This key can be enabled or disabled when operating from a source
different tan the operator by setting parameter o2-02.
STOP Key
EN-14
Power Up and Basic Parameter Setup
‹ Start Up Procedure
START
Installation
Wiring
Set power supply
voltage jumper *1
Turn ON power
Confirm status
Basic settings
(Quick programming mode)
Select control
method.
NO
Vector Control (A1-02 = 2 or 3) *5
V/f control
YES
YES
V/f Control with PG (A1-02 = 1
PG?
NO
V/f control
Set E1-03, E2-04 and F1-01.
*2
Set E1-03.
V/f default: 200V/50Hz (400V/50Hz)
V/f default: 200V/50Hz (400V/50Hz)
Settings according
to control mode
Motor
operation possible
during autotuning?
*3
NO
YES
*6
Non-rotating autotuning
*4
*6
Rotating
Non-rotating
for line-to-line resistance
autotuning
autotuning
Application settings
(Advanced programming mode)
1.Set for 400 V Class Inverter for 75 kW or more.
2.If there is a reduction gear between the motor and PG, set the
reduction ratio in F1-12 and F1-13 in advanced programming
mode.
No-load
operation
3.Use rotational autotuning to increase autotuning accuracy
whenever it is okay for the motor to be operated.
4.If the motor cable changes to 50 m or longer for the actual
installation, perform non-rotating autotuning for the line-to-line
resistance only on site.
Loaded
operation
Optimum adjustments
and parameter settings
5.The default control mode is Open Loop Vector control
(A1-02=2).
Check/record
6.If the maximum output frequency and the base frequency are
different, set the maximum output frequency (E1-04) after
autotuning.
parameter settings
END
Fig 8 Trial Operation Flowchart
EN-15
‹ Before Power Up
The following points should be checked carefully before the power is switched on.
• Check if the power supply meets the inverter specification.
• Check if the power supply cables are tightly connected to the right terminals (L1, L2, L3).
• Check if the motor cables are tightly connected to the right terminals on the inverter side (U, V,
W) as well as on the motor side.
• Check if the braking unit / braking resistor is connected correctly.
• Check if the Inverter control circuit terminal and the control device are wired correctly.
• Set all Inverter control circuit terminals to OFF.
• When a PG card is used, check if it is wired correctly.
‹ Display after Power Up
After normal power up without any problems the operator display shows the following messages
Rdy
-DRIVE-
Frequency Ref
Display for normal
operation
The frequency reference monitor is dis-
played in the data display section.
U1- 01=50.00Hz
U1-02=50.00Hz
U1-03=10.05A
When a fault has occurred or an alarm is active a fault or alarm message will appear. In this case,
-DRIVE-
A fault or alarm message is shown on the
display.
The example shows a low voltage alarm.
UV
Display for fault operation
DC Bus Undervolt
‹ Autotuning
Autotuning sets motor parameters automatically when using Open Loop or Closed Loop Vector con-
trol, when the cable length is long or the installation has changed.
„ Setting the Autotuning Mode
One of the following three autotuning modes can be set.
• Rotating autotuning
• Non-rotating autotuning
• Non-rotating autotuning for line-to-line resistance only
Rotating Autotuning (T1-01 = 0)
Rotating autotuning is used for Open Loop and Closed Loop Vector control only. Set T1-01 to 0,
input the data from the motor nameplate, and then press the RUN key on the Digital Operator. The
Inverter will operate the motor for approximately 1 minute and set the required motor parameters
automatically.
Non-rotating Autotuning (T1-01 = 1)
Non-rotating autotuning is used for Open Loop and Closed Loop Vector control only. Set T1-01 to 1,
input the data from the motor nameplate, and then press the RUN key on the Digital Operator. The
inverter will supply power to the non-rotating motor for approximately 1 minute and some of the
EN-16
motor parameters will be set automatically. The remaining motor parameters will be set automati-
cally during the first time operation.
Non-rotating Autotuning for Line-to-Line Resistance (T1-01 = 2)
Non-rotating autotuning for line-to-line resistance can be used in any control mode. This is the only
possible autotuning for V/f control and V/f control with PG.
It can be used to improve the performance when the motor cable is long, the cable length has
changed or when the motor and inverter have different capacities.
To perform autotuning in V/f control or V/f control with PG, set T1-02 (Motor rated power) and T1-04
(Motor rated current) and then press the RUN key on the Digital Operator. The Inverter will supply
power to the non-rotating motor for approximately 20 seconds and the Motor line-to-line resistance
and cable resistance will be automatically measured.
1. Power will be supplied to the motor during autotuning but the motor will not turn. Do not touch the motor
until autotuning has been completed.
2. Ensure that all motor contactors are closed before the autotuning is started.
3. To cancel autotuning press the STOP key on the Digital Operator.
IMPORTANT
„Other Alarms and Faults During Autotuning
For an overview of possible autotuning alarms or faults and corrective actions refer to page 24, Auto-
EN-17
User Parameter
Param-
eter
Num-
ber
Param-
eter
Num-
Name
Description
Name
Description
ber
Motor Slip Compensation (not available in V/f with
PG)
Initialize Data
Language
selection for
Used to improve speed accuracy
0:English
2:German
3:French
Slip compensa-
tion gain
•
•
Increase if output frequency is too low
Decrease if output frequency is too
high.
C3-01
C3-02
Digital Opera-
tor dis-
A1-00
4:Italian
5:Spanish
6:Portuguese
play(JVOP-
160-OY only)
Sets the slip compensation delay time
•
Slip compensa-
tion delay time
(only available
in V/f and OLV)
Increase if output frequency is not
stable
Decrease setting when slip compen-
sation responsiveness is low.
0:Monitoring only (Monitoring drive
mode and setting A1-01 and A1-04.)
1:Used to select user parameters (Only
parameters set in A2-01 to A2-32 can
be read and set.)
•
Parameter
A1-01
Speed Control (ASR) (only available in V/f with PG
and CLV)
2:Advanced
access level
(Parameters can be read and set in
both, quick programming mode (Q)
and advanced programming mode
(A).
ASR propor-
tional gain 1
Sets the proportional gain of the speed
loop (ASR)
C5-01
0:V/f control
ASR integral
time 1
Sets the integral time of the speed loop
(ASR)
C5-02
Control method
A1-02
1:V/f control with PG
2:Open loop vector control
3:Closed loop vector control
selection
P,I
ASR propor-
tional gain 2
P = C5-01
I = C5-02
C5-03
0: No initializing
1110:Initializes using the user
parameters
2220:Initializes using a two-wire
sequence. (Initializes to the factory
setting.)
3330: Initializes using a three-wire
sequence.
P = C5-03
I = C5-04
ASR integral
time 2
C5-04
C5-06
Motor
speed (Hz)
A1-03 Initialize
0
E1-04
ASR delay time
(only CLV)
Sets the ASR filter time constant.
ASR switching Sets the frequency for switching
C5-07 frequency
(only CLV)
Sequence / Reference Source
between ASR gain 1, 2 and ASR integral
time 1, 2
Sets the frequency reference input
method.
0:Digital Operator
1:Control circuit terminal (analog input)
2:Serial communication (RS422 / 485)
3:Option Card
Reference
b1-01 source selec-
tion
ASR integral
C5-08 limit
Sets the limit for the integral part of the
ASR controller.
(only CLV)
Carrier Frequency
Sets the run command input method.
0:Heavy Duty
1:Normal Duty 1
2:Normal Duty 2
Heavy/Normal
C6-01
RUN com-
b1-02 mand source
selection
0:Digital Operator
duty selection
1:Control circuit terminal (digital inputs)
2:Serial communication (RS422 / 485)
3:Option Card
Selects the carrier frequency (factory
setting depends on Inverter capacity)
Selects the stopping method when the
Run signal is removed
0:Deceleration to stop
1:Coast to stop
2:DC injection to stop
3:Coast to stop with timer (New Run
commands are disregarded while
coasting.)
0: Low noise, low carrier
1: 2.0 kHz
Carrier fre-
C6-02 quency selec-
tion
Stopping
b1-03 method selec-
tion
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
F: Programmable pattern
0:Reverse enabled
Speed Settings
1:Reverse disabled
Prohibition of
b1-04 reverse opera-
tion
Multi speed
references 1 to
16
d1-01
to
d1-16
2:Output Phase Rotation (both rota-
tional directions are enabled)
3:Output Phase Rotation with Reverse
disabled.
Sets the multi-step speed references.
Jog frequency
reference
d1-17
Acceleration / Deceleration Settings
Acceleration/
Deceleration
times
Sets the time to accelerate/decelerate
from 0 Hz to the maximum output fre-
quency.
Torque Control (only available in CLV)
C1-
††
Torque control
selection
0:Speed control
1:Torque control
d5-01
S-Curve Settings
Sets the delay from inputting a “speed/
torque control change” signal (by digital
input) until the control is acutally
changed
Speed/torque
d5-06 control switch
over timer
S-curve char-
acteristic time
at acceleration
Sets the S-curve characteristic at accel-
eration start and end.
C2-
††
V/f Pattern Settings
Input voltage
setting
This setting is used as a reference value
for protection functions.
E1-01
EN-18
Param-
eter
Num-
ber
Param-
eter
Num-
ber
Name
Description
Name
Description
Selects on which terminal the main
frequency reference can be input.
0:Use analog input 1 on terminal
A1 for main frequency reference.
1:Use analog input 2 on terminal A2
for main frequency reference.
Output Voltage (V)
Max. output
E1-04 frequency
(FMAX)
Terminal A1/
A2 switching
H3-13
Max. output
E1-05 voltage
(VMAX)
Terminal FM
H4-01 monitor selec-
tion
Sets the number of the monitor item
to be output (U1-††) at terminal FM/
AM.
Terminal AM
H4-04 monitor selec-
tion
Frequency (Hz)
Base fre-
E1-06
To set V/f characteristics in a straight
line, set the same values for E1-07
and E1-09. In this case, the setting for
E1-08 will be disregarded.
Always ensure that the four frequen-
cies are set in the following order:
E1-04 (FMAX) ≥ E1-06 (FA) > E1-07
(FB) ≥ E1-09 (FMIN)
quency (FA)
Pulse Train I/O
Selects the pulse train input function
0:Frequency reference
1:PID feedback value
Pulse train
H6-01 input function
selection
Base Voltage
E1-13
2:PID target value
(VBASE)
Sets the number of pulses in Hz that
is equivalent to 100% of the input item
selected in H6-01.
Pulse train
H6-02
Motor Data Settings
input scaling
Motor rated
current
E2-01
Pulse train
H6-06 monitor selec-
tion
Selects the pulse train monitor output
item (U1-††)
Motor rated
E2-02
slip
Pulse monitor Sets the number of pulses output in
H6-07
Motor no-load
E2-03
scaling
Hz when the monitor item is 100%.
current
Stall Prevention
Sets the motor data.
Number of
E2-04
0:Disabled (Acceleration as set.
With a heavy load, the motor may
stall.)
1:Enabled (Acceleration stopped
when L3-02 level is exceeded.
Acceleration starts again when the
current has fallen below the stall
prevention level).
2:Intelligent acceleration mode (Using
the L3-02 level as a basis, accelera-
tion is automatically adjusted. Set
acceleration time is disregarded.)
motor poles
Motor
E2-09 mechanical
losses
Stall preven-
tion selection
L3-01 during accel
(not available
Motor rated
E2-11
output power
in CLV)
PG Option Setup
Sets the number of PG pulses per
revolution
F1-01 PG constant
0:Phase A leads with forward run
command
1:Phase B leads with forward run
command
0:Disabled (Deceleration as set. If
deceleration time is too short, a
DC bus overvoltage may result.)
1:Enabled (Deceleration is stopped
when the DC bus voltage exceeds
the stall prevention level. Decelera-
tion restarts when the voltage falls
below the stall prevention level
again.)
2:Intelligent deceleration mode
(Deceleration rate is automatically
adjusted so that the Inverter can
decelerate in the shortest possible
time. The set deceleration time is
disregarded.)
F1-05 PG rotation
Digital I/O Settings
Terminal S3 to Refer to page 20, Digital Input Func-
H1-01
to
H1-05
S7 function
selection
tion Selections (H1-01 to H1-05) for a
list of selections
Stall preven-
L3-04 tion selection
during decel
Terminal M1-
M2 and M3-
M4 function
selection
H2-01
and
H2-02
Refer to page 20, Digital Output Func-
tion Selections for a list of selections
Analog I/O Settings
Selects the signal level input at multi-
function analog input A2.
0:0 to +10 V (11 bit).
3:Enabled with braking resistor
Fault Restart
Analog input
H3-08 A2 signal level
selection
Sets the number of auto restart
attempts.
Automatically restarts after a fault and
conducts a speed search from the run
frequency.
1:-10 to +10 V
Number of
L5-01 auto restart
attempts
2:4 to 20 mA (9-bit input).
Ensure to switch S1-2 to “V” before
using a voltage input.
Analog input
H3-09 A2 function
selection.
Selects the multi-function analog
input function for terminal A2.
Sets whether a fault relay is activated
during fault restart.
0:No output (Fault relay is not acti-
vated.)
1:Output (Fault relay is activated.)
Auto restart
L5-02 operation
selection
EN-19
Param-
eter
Num-
ber
Param-
eter
Num-
ber
Name
Description
Name
Description
Fault Trace Data
Torque Limit (only OLV and CLV)
U2-01 Current fault
Forward drive Sets the torque limit vlaue as a per-
L7-01
torque limit
centage of the motor rated torque.
U2-02 Last fault
Four individual regions can be set.
Reverse drive
torque limit
U2-03 Reference frequency at fault
U2-04 Output frequency at fault
U2-05 Output current at fault
L7-02
Output torque
Positive torque
Forward
L7-03 regenerative
torque limit
No.
o
motor
Regen.
U2-07 Output voltage reference at fault
U2-08 DC bus voltage at fault
U2-09 Output power at fault
U2-11 Input terminal status at fault
U2-12 Output terminal status at fault
U2-13 Operation status at fault
U2-14 Cumulative operation time at fault
Fault History Data
rotations
Reverse
Forward
Regen.
Reverse
L7-04 regenerativ
torque limit
Negative torque
Monitor Data
U1-01 Frequency reference in Hz / rpm
U1-02 Output frequency in Hz / rpm
U1-03 Output current in A
U3-01
to
U1-06 Output voltage in VAC
U1-07 DC bus voltage in VDC
U1-08 Output power in kW
Last fault to fourth last fault
U3-04
U3-05
to
U3-08
Cumulative operation time at fault 1 to 4
Fifth last to tenth last fault
U1-09 Torque reference
Shows input ON/OFF status.
U1-10 =
U3-09
to
1: FWD command
(S1) is ON
U3-14
1: REV command
(S2) is ON
1: Multi input 1
(S3) is ON
U3-15
to
U3-20
Accumulated time of fifth to tenth fault
Input terminal
status
U1-10
1: Multi input 2
(S4) is ON
1: Multi input 3
(S5) is ON
1: Multi input 4
(S6) is ON
1: Multi input 5
(S7) is O N
* The following faults are not recorded in the error log:
CPF00, 01, 02, 03, UV1, and UV2.
Digital Input Function Selections (H1-01 to H1-05)
3
4
5
Multi-step speed reference 1
Multi-step speed reference 2
Mulit-step speed reference 3
Shows output ON/OFF status.
U1-11 =
Jog frequency command (higher priority than multi-
step speed reference)
6
1: Multi-function
contact output 1
(M1-M2) is ON
1: Multi-function
contact output 2
(M3-M4) is ON
1: Multi-function
contact output 3
(M5-M6) is ON
Not used
7
F
Accel/decel time selection 1
Not used (Set when a terminal is not used)
Fault reset (Reset when turned ON)
PI control disable
Output termi-
nal status
14
19
U1-11
External fault; Input mode: NO contact/NC contact,
Detection mode: Normal/during operation
20 to
2F
(Always 0).
1: Error output
(MA/MB-MC) is ON
71
77
Speed/torque control change (ON: Torque control)
Speed control (ASR) gain switching (ON: C5-03)
Inverter operating status.
Digital Output Function Selections
(H2-01 and H2-02
U1-12 =
Run
During run 1 (ON: run command is ON or voltage is
0
being output)
1: Zero speed
Inverter operation ready; READY: After initialization or
no faults
1: Reverse
6
Operation sta-
tus
U1-12
1: Reset signal input
1: Speed agree
1: Inverter ready
1: Minor fault
F
Not used. (Set when the terminal is not used.)
Minor fault (Alarm) (ON: Alarm displayed)
During reverse run (ON: During reverse run)
10
1A
Motor overload (OL1, including OH3) pre-alarm (ON:
90% or more of the detection level)
1F
30
1: Major fault
U1-13 Cumulative operation time in hrs.
U1-21 ASR input
During torque limit (current limit) (ON: During torque
limit)
Activated if the ASR is operating for torque limit. The
ASR output becomes the torque reference, the motor
is rotating at the speed limit.
U1-22 ASR output
32
U1-34 OPE fault parameter
U1-40 Cooling fan operating time in hrs.
EN-20
Troubleshooting
‹ General Faults and Alarms
Faults and Alarms indicate unsusal inverter / application conditions.
An alarm does not necessarily switch off the inverter but a message is displayed on the keypad (i.e.
a flashing alarm code) and an alarm output can be generated at the multi-function outputs (H2-01
and H2-02) if programmed. An alarm automatically disappears if the alarm condition is not present
anymore.
A fault switches the inverter output off immediately, a message is displayed on the keypad and the
fault output is switched. The fault must be reset manually after the cause and the RUN signal have
been removed.
The following table shows a list of faults and alarms with their corrective actions.
Alarm Fault
Display
Meaning
Corrective Actions
Option Card Communication Alarm
After initial communication was established, the
connection was lost.
Check the connections and all user-side soft-
ware configurations.
BUS
Option Com Err
Control Fault
A torque limit was reached continuously for 3
seconds or longer during a deceleration stop in
Open Loop Vector control
CF
Check the motor parameters
Out of Control
CPF00
COM-
ERR(OP&INV)
Digital Operator Communication Fault 1/2
• Communication fault between Operator and
Inverter
• Disconnect the Digital Operator and then
connect it again.
• Cycle the Inverter power supply.
• Replace the Inverter.
CPF01
COM-
• CPU External RAM Fault
ERR(OP&INV)
CPF02 Fault
Baseblock circuit error
CPF02
BB Circuit Err
• Perform an initialization to factory defaults.
• Cycle the Inverter power supply.
• Replace the Inverter.
CPF03
EEPROM error
CPF03
EEPROM Error
CPF04
CPF04
INternal A/D Err
CPU Internal A/D Converter Fault
F1-04 = 0, 1 or 2 and A1-02 = 1 or 3
The speed deviation has been greater than the
setting in F1-10 for a time longer than the setting
F1-11.
• Reduce the load.
• Lengthen the acceleration and deceleration
time
• Check the mechanical system
• Check the settings of F1-10 and F1-11
• Check the sequence and if the brake is
opened when the inverter starts to increase
the speed.
DEV
Speed Deviation
F1-04 = 3 and A1-02 = 1 or 3
The speed deviation has been greater than the
setting in F1-10 for a time longer than the setting
F1-11.
Forward/Reverse Run Commands Input
Together
Both the forward and the reverse run commands
are input simultaneously for 500ms or more.
This alarm stops the motor.
EF
Check external sequence logic, so that only
one input is activated at a time.
External Fault
• Check for an external fault condition.
• Verify the parameters.
• Verify communication signals
External fault input from Communications
Option Card
EF0
Opt External Flt
External fault at terminal Sx (x stands for termi- Eliminate the cause of the external fault con-
nals S3 to S7) dition.
EFx
Ext Fault Sx
Detected after a fault when a RESET command Remove the RUN signal first and reset the
is input while the RUN command is still active error.
Ext Run Active
Cannot Reset
• Remove the motor and run the Inverter
without the motor.
Ground Fault
The ground current at the Inverter output
• Check the motor for a phase to ground
short.
GF
Ground Fault
exceeded 50% of the Inverter rated output cur- • Check the output current with a clampmeter
rent and L8-09=1 (Enabled).
to verify the DCCT reading.
• Check the control sequence for wrong
motor contactor signals.
EN-21
Alarm Fault
Display
Meaning
Corrective Actions
• Remove the motor and run the Inverter
without the motor.
Over Current
• Check the motor for a phase-to-phase
OC
Over Current
The Inverter’s output current exceeded the over- short.
current detection level.
• Verify the accel/decel times (C1-††).
• Check the Inverter for a phase-to-phase
short at the output.
Heatsink Overheat
L8-03 = 0,1 or 2 and the temperature of the
Inverter's cooling fin exceeded the L8-02 value.
• Check for dirt build-up on the fans or heat-
sink.
• Reduce the ambient temperature around
the drive.
OH
Inverter's Cooling Fan Stopped
Heatsnk Overtemp
L8-03 = 3 or 4 and the temperature of the
Inverter's cooling fin exceeded the L8-02 value.
• Replace the cooling fan(s).
Heatsink Overheat
The temperature of the Inverter’s heatsink
exceeded 105 °C.
• Check for dirt build-up on the fans or heat-
sink.
• Reduce the ambient temperature around
the drive.
OH1
Heatsink Max Temp
Inverter’s Cooling Fan Stopped
• Replace the cooling fan(s).
Motor Overload
Detected when L1-01 is set to 1,2 or 3 and the
Inverter’s I²t value exceeded the motor overload
curve.
The overload curve is adjustable using parame-
ter
E2-01 (Motor Rated Current), L1-01 (Motor Pro-
tection Selection) and L2-02 (Motor Protection
Time Constant)
• Recheck the cycle time and the size of the
load as well as the accel/decel times (C1-
††).
• Check the V/f characteristics (E1-††).
• Check the setting of Motor Rated Current
Setting (E2-01).
OL1
Motor Overload
• Recheck the cycle time and the size of the
load as well as the accel/decel times (C1-
††).
• Check the V/f Characteristics (E1-††).
• Check if the inverter rated current matches
the motor rated current.
Inverter Overload
The Inverter output current exceeded the Invert-
ers’s overload capability
OL2
Inv Overload
F1-03 = 0, 1 or 2 and A1-02 = 1 or 3
The motor speed feedback (U1-05) exceeded
the setting in F1-08 for a time longer than the
setting of
• Adjust the ASR settings in the C5 parame-
ter groupt
• Check the reference circuit and reference
gain.
F1-09
OS
Overspeed Det.
F1-03 = 3 and A1-02 = 1 or 3
The motor speed feedback (U1-05) exceeded
the setting in F1-08 for a time longer than the
setting of
• Check the settings in F1-08 and F1-09
F1-09
• Increase the deceleration time (C1-02/04)
or connect a braking option.
• Check the power supply and decrease the
voltage to meet the inverter’s specifica-
tions.
The DC bus voltage has exceeded the overvolt-
age detection level.
Default detection levels are:
200 V class: 410 VDC
(onlyin
OV
stop
condi-
tio)
DC Bus Overvolt
400 V class: 820 VDC
• Check the braking chopper / resistor.
Input Phase Loss
Too big DC bus voltage ripple.
Only detected when L8-05=1 (enabled)
• Tighten the input terminal screws
• Check the power supply voltage
PF
Input Phase Loss
PG Disconnection
Detected when F1-02 = 0, 1 or 2 and A1-02 = 1
or 3.
Detected when no PG (encoder) pulses have
been received for a time longer than the setting
in F1-14.
• Fix the broken/disconnected wiring.
• Supply power to the PG properly.
• Check the sequence and if the brake is
opened when the inverter starts to increase
the speed.
PGO
PG Open
PG Disconnection
Detected when F1-02 = 3 and A1-02 = 1 or 3.
PG (encoder) pulses have not been received for
a time longer than the setting in F1-14.
EN-22
Alarm Fault
Display
Meaning
Corrective Actions
DC Bus Fuse Open
The fuse in the main circuit is blown.
Warning:
• Check the motor and the motor cables for
short circuits or insulation failures (phase-
to-phase).
PUF
DC Bus Fuse Open
PG (encoder) pulses have not been received for • Replace the inverter after correcting the
a time longer than the setting in F1-14.
fault.
Dynamic Braking Transistor
The built-in dynamic braking transistor failed
• Cycle power to the inverter.
• Replace the inverter.
RR
DynBrk Transistr
The DC bus voltage is below the Undervoltage • Check the input voltage.
Detection Level
• Check the wiring of the input terminals.
• Check the input voltage and the wiring of
the input terminals.
(L2-05). The default settings are:
200V class: 190 VDC
400 V class: 380 VDC
(onlyin
UV1
stop
condi-
tio)
DC Bus Undervolt
• Extend the settings in C1-01/03
Main Circuit MC Operation Failure
No MC response during Inverter operation.
Replace the Inverter.
Control Power Supply Undervoltage
Undervoltage of the control circuit while the
Inverter was running.
• Remove all connection to the control termi-
nals and cycle the power to the Inverter.
• Replace the Inverter.
UV2
CTL PS Undervolt
‹ Operator Programming Errors
An Operator Programming Error (OPE) occurs when two or more parameter related to each other
are set inappropriately or an individual parameter setting is incorrect. The Inverter does not operate
until the parameter setting is corrected; however, no other alarm or fault output will occur. If an OPE
occurs, change the related parameter by checking the cause shown in the table below. When an
OPE error is displayed, press the ENTER key to see U1-34 (OPE Detected). This monitor displays
the parameter that is causing the OPE error.
Display
Meaning
Corrective Actions
OPE01
kVA Selection
Inverter kVA Setting Error
Enter the correct kVA setting in o2-04.
OPE02
Limit
Parameter setting is out of its range
Verify the parameter settings.
One of the following errors has been made in the multi-
function input (H1-01 to H1-05) settings:
• Duplicate functions were selected.
• UP/DOWN Command(10 and 11) were not selected
simultaneously.
• The up/down commands (10 and 11) and Accel/
Decel Ramp Hold (A) were selected at the same
time.
• More than one of the Speed Search inputs (61, 62,
64) were set simultaneously.
• External Baseblock NO (8) and External Baseblock
NC (9) were selected at the same time.
• The up/down commands (10 and 11) were selected
while PID Control was enabled.
OPE03
Terminal
Verify the parameter settings in H1-††
• The Emergency Stop Command NO (15) and NC(17)
are set simultaneously.
• PID is enabled and UP and/or DOWN (10 / 11) com-
mand are set.
• HSB (68) and KEB (65/66) command are set simulta-
neously.
RUN/Reference Command Selection Error
• Verify that the board is installed. Remove the power
supply and re-install the option board again
• Recheck the setting of b1-01 and b1-02
The Reference Source Selection b1-01 and/or the RUN
Source Selection parameter b1-02 are set to 3 (option
board) but no option board is installed.
OPE05
Sequence Select
Control Method Selection Error
One of the control methods needing a PG feedback
Verify the control method selection in parameter A1-02
OPE06
PG Opt Missing
was selected (A1-02 = 1 or 3), but a PG option board is and/or the installation of the PG option board.
not installed.
EN-23
Display
Meaning
Function Selection Error
Corrective Actions
A setting has been made that is applicable with the cur-
rent control method.
Example: A function used only with open loop vector
control was selected for V/f control.
OPE08
Constant Selection
Verify the control method and the function.
Check parameters (E1-††). A frequency/voltage value
may be set higher than the maximum frequency/voltage.
OPE010
V/f Ptrn Setting
V/f Parameter Setting Error
‹ Autotuning Faults
Autotuning faults are shown below. When the following faults are detected, the fault is displayed on
the digital operator and the motor coasts to stop. No fault or alarm outputs will be operated.
Display
Meaning
Corrective Actions
• Check the input data.
• Check the Inverter and motor capacity.
• Check the motor rated current and no-load current set-
ting.
Er-01
Fault
Motor data fault
• Check the input data.
• Check wiring and the machine.
• Check the load.
Er-02
Minor Fault
Alarm
Er-03
STOP key
STOP key input
-
Line-to-Line Resistance Fault
Autotuning result is outside the parameter setting
range.
Er-04
Resistance
• Check the input data.
No-Load Current Fault
Autotuning result is outside the parameter setting
range.
• Check the motor wiring.
Er-05
No-Load Current
• If the motor is connected to the machine, disconnect it.
• If the setting of T1-03 is higher than the Inverter input
power supply voltage (E1-01), change the input data.
Rated Slip Fault
Autotuning result is outside the parameter setting
range.
Er-08
Rated slip
Acceleration Fault (Rotating autotuning only)
The motor did not accelerate in the specified time
(C1-10+10sec.)
• Increase C1-01(Acceleration time)
• Increase L7-01 and L7-02 (Torque limits)
• If the motor is connected to the machine, disconnect it.
Er-09
Accelerate
Motor Speed Fault (Rotating autotuning only)
• If the motor is connected to the machine, disconnect it.
The torque reference exceeded 100% during accel- • Increase C1-01
Er-11
Motor Speed
eration. Deteceted only when A1-02 = 2 or 3 (Vector • Check the input data (particularly the number of PG
control modes).
pulses and the number of motor poles)
Current Detection Fault
• The current exceeded the motor rated current.
• Any of U/T1, V/T2 and W/T3 has open-phase.
Er-12
I-det. Circuit
Check wiring of the Inverter and the mounting.
Leakage Inductance Fault
Er-13
Leakage Induc- Autotuning result is outside the parameter setting
Check motor wiring.
tance Fault
range.
Rated Current Setting Alarm
Displayed after auto-tuning is complete
During auto-tuning, the measured value of motor
rated current (E2-01) was higher than the set value.
End-1
V/f Over Setting
Check the motor rated current value.
• Check the input data
• Check the motor wiring.
• If the motor is connected to the machine, disconnect it.
Motor Core Saturation Alarm
(only for rotating autotuning)
End-2
Saturation
Rated Current Setting Alarm
During autotuning the measured value of motor rated Check the motor rated current value
current (E2-01) was greater than the set value.
End-3
Rated FLA Alm
EN-24
|
Miller Electric Welder MW 4150 User Manual
Multiquip Portable Generator DCA180SSJU User Manual
Musical Fidelity Stereo Amplifier A308 CR User Manual
NEC Telephone AT 35 User Manual
NETGEAR Network Router DGND4000 100NAS User Manual
New Buck Corporation Indoor Fireplace 42ZCBB User Manual
Optiview DVR 22806 437 User Manual
Oricom Cordless Telephone ECO80 User Manual
Panasonic CD Player CF VCD711 User Manual
Panasonic Impact Driver EY6506 User Manual